Thermal Degasser System
MESANN Thermal Degasser
Free Oxygen (O2) and Carbon Dioxide (CO2) gases dissolved in the boiler feedwater cause damage to the metal surfaces of the boiler and steam system. To remove these corrosive gases from the feedwater, the feedwater is separated into small droplets and heated with steam, causing the CO2 to evaporate at 60°C and the O2 to evaporate above 100°C. In a conventional thermal degasser system, the process of separating the feedwater into small droplets is done by a sprinkler system.
To prevent evaporation and cavitation at the feedwater pump suction point, the water level in the degasser must be at least 6 m above the pump suction inlet.
Thermal Degasser Equipment
Degasser Tank and Dome
Safety Valve
Pressure Reducers and Equipment
Valve Assembly
Heating Coil and Control Valve Equipment
Indicators and other equipment

MESANN reserves the right to make changes to the dimensions of its products.

Klasik Termik Degazör

Klasik Termik Degazör

Klasik Termik Degazör

Klasik Termik Degazör

Klasik Termik Degazör

Klasik Termik Degazör